Analysis and Reduced of Grid-Connected and Islanding in Resonance Propagation

Ralla Ramya, Bomma Shwetha, Bandi Sumalatha

Abstract


The application of underground cables and shunt capacitor banks may introduce power distribution system resonances. In this paper, the impacts of voltage-controlled and current-controlled distributed generation (DG) units to micro grid resonance propagation are compared. It can be seen that a conventional voltage-controlled DG unit with an LC filter has a short-circuit feature at the selected harmonic frequencies, while a current-controlled DG unit presents an open-circuit characteristic. Due to different behaviors at harmonic frequencies, specific harmonic mitigation methods shall be developed for current controlled and voltage-controlled DG units, respectively. This paper also focuses on developing a voltage-controlled DG unit-based active harmonic damping method for grid-connected and islanding micro grid systems. An improved virtual impedance control method with a virtual damping resistor and a nonlinear virtual capacitor is proposed. The nonlinear virtual capacitor is used to compensate the harmonic voltage drop on the grid-side inductor of a DG unit LCL filter. The virtual resistor is mainly responsible for micro grid resonance damping. The effectiveness of the proposed damping method is examined using both a single DG unit and multiple parallel DG units.